Mitsubishi Electric 800 Series Instruction Manual page 192

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• The following table shows the command interface for each function in the Network operation mode, determined by the
parameter settings: an external terminal or a communication interface (PU connector, Ethernet connector, or
communication option).
Pr.338 Communication operation command source
Pr.339 Communication speed command source
Frequency setting through communication
Terminal 2
Terminal 4
Low-speed operation command/Remote setting
*1
RL
(setting clear)/Stop-on-contact selection 0
Middle-speed operation command/Remote
*1
RM
setting (deceleration)
High-speed operation command/ Remote setting
*1
RH
(acceleration)
Second function selection/ Stop-on-contact
*1
RT
selection 1
*1
Terminal 4 input selection
AU
*1
Jog operation selection
JOG
*1
External thermal relay input
OH
*1
15-speed selection
REX
*1
Inverter run enable
X10
*1
PU operation external interlock
X12
*1
PID control valid
X14
*1
Brake opening completion
BRI
*1
PU/External operation switchover
X16
*1
V/F switchover
X18
Output stop
*1
MRS
PU operation interlock
STP
Start self-holding selection
*1
(STOP)
*1
Control mode switchover
MC
*1
Torque limit selection
TL
*1
JOG2
*1
Traverse function selection
X37
*1
Trace trigger input
TRG
*1
Trace sampling start/end
TRC
*1
Sequence start
SQ
*1
Fault clear
X51
*1
Forward rotation command
STF
*1
Reverse rotation command
STR
*1
Inverter reset
RES
*1
PU/NET operation switchover
X65
*1
External/NET operation switchover
X66
*1
Command source switchover
X67
*1
PID P control switchover
X72
*1
Emergency stop
X92
*1
Use Pr.178 to Pr.189 (Input terminal function selection) to assign the function to an input terminal. (Refer to
[Explanation of Terms in Table]
EXT: External terminal only
NET: Communication interface only
Combined: Either external terminal or communication interface
—: Neither external terminal nor communication interface
0: NET
0:
1:
NET
EXT
NET —
EXT
EXT
NET EXT
NET EXT
NET EXT
NET
Combined
EXT
NET EXT
EXT
EXT
NET EXT
NET
EXT
NET
Combined
EXT
NET
NET
NET
NET
Combined
Combined
EXT or NET
Combined
NET
NET
EXT
EXT
EXT
EXT
NET EXT
Combined
9.3 Start command source and frequency command source during communication operation
1: EXT
2:
0:
1:
2:
EXT
NET
EXT
EXT
NET NET —
NET
EXT
EXT
NET EXT
Pr.59 = "0" (multi-speed), Pr.59
NET EXT
≠ "0" (remote), Pr.270 ="1" (stop-
on-contact)
NET EXT
Pr.270 = "1" (stop-on-contact)
EXT
Combined
EXT
Pr.59 ="0" (multi-speed)
NET EXT
NET EXT
EXT
EXT
EXT
Pr.79 ≠ "7"
Pr.79 = "7".
When X12 signal is not assigned.
EXT
EXT
EXT
EXT
EXT
EXT
EXT
Pr.414 = "1": Valid when there is
EXT
external or network input.
Pr.414 = "2": External.
EXT
EXT
EXT
NET EXT
EXT
9. (D) Operation Command and Frequency Command
Remarks
10
page
283.)
191
1
2
3
4
5
6
7
8
9

Advertisement

Table of Contents