Earth (Ground) Fault Detection At Start - Mitsubishi Electric 800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

10.3

Earth (ground) fault detection at start

Select whether to make earth (ground) fault detection at start. When enabled, earth (ground) fault detection is performed
immediately after a start signal input to the inverter.
Pr.
249
Earth (ground) fault detection at
H101
start
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
• If a ground fault is detected at start while Pr.249 = "1", the output-side earth (ground) fault overcurrent (E.GF) is displayed
and the outputs are shut off.
• When the Pr.72 PWM frequency selection setting is high, enable the ground fault detection at start.
NOTE
• Because the detection is performed at start, output is delayed for approx. 20 ms every start.
• Use Pr.249 to enable/disable ground fault detection at operation start.
204
10. (H) Protective Function Parameters
10.3 Earth (ground) fault detection at start
Initial value
Name
Gr.1
0
*1
Setting range
Gr.2
0
1
1
page
82).
Description
Earth (ground) fault detection at start
disabled
Earth (ground) fault detection at start
enabled

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents