Changing The Frequency (Initial Value: 60 Hz) At The Maximum Voltage Input (Initial Value: 5 V) - Mitsubishi Electric 800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF/DI0 terminal function selection must be set to "60" (or Pr.179 STR/DI1 terminal function selection must be
set to "61") (initial value).
• When terminal 10 is used, the maximum output frequency may fluctuate in a range of ±6 Hz due to fluctuations in the output
voltage (5 ±0.5 VDC). Use Pr.125 or C4 to adjust the output frequency at the maximum analog input as required. (Refer to
page
273.)
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function
2.6.4
Changing the frequency (initial value: 60 Hz) at the
maximum voltage input (initial value: 5 V)
• Change the maximum frequency.
The following shows the procedure to change the frequency at 5 V from 60 Hz (initial value) to 50 Hz using a frequency setting
potentiometer for 0 to 5 VDC input. Set 50 Hz in Pr.125 so that the inverter outputs 50 Hz at 5 V input.
Operating procedure
1.
Selecting the parameter
Turn the setting dial or press the UP/DOWN key until "P.125" (Pr.125) appears.
Press the SET key to show the present set value (60.00 Hz).
2.
Changing the maximum frequency
Turn the setting dial or press the UP/DOWN key to change the value to "50.00" (50.00 Hz).
Press the SET key to confirm the setting. "50.00" blinks.
3.
Selecting the mode and the monitor item
Press the MODE key twice to select the monitor mode and to monitor a frequency.
4.
Start
Turn ON the start switch (STF/STR signal), and turn the frequency setting potentiometer clockwise slowly to full.
(Refer to steps 2 and 3 in 2.6.3.)
The motor is operated at 50 Hz.
NOTE
• To change the frequency at the input of 0 V (minimum voltage), use the calibration parameter C2.
timepage 158
60Hz
(50Hz)
Output frequency
(Hz)
Bias
C2
0
0
Frequency setting signal
0
C3
selectionpage 283
Initial value
Gain
Pr.125
100%
5V
10V
C4
2.6 Basic operation procedure (External operation)
1
2
3
4
5
6
7
8
9
10
41
2. Basic Operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents