F-DI/F-DO configuration

Inputs screen F-DI
Figure 8-9
Inputs screen
NC/NO contact (p10040)
Terminal property F-DI 0-9 (p10040.0 = F-DI 0, ... p10040.9 = F-DI 9), only the property of
the second (lower) digital input is set. Always connect an NC contact to digital input 1
(upper). Digital input 2 can be configured as NO contact.
Activate test mode (p10041)
A check mark at an F-DI defines whether the pair of digital inputs is to be integrated in the
forced dormant error detection test of the assigned power supply (L1+ or L2+) (for additional
information, see chapter "Forced dormant error detection", under Extended Functions).
LED in F-DI screen
The LED downstream of the AND element indicates the logical state (inactive: gray, active:
green, discrepancy error: red).
Safety Integrated
Function Manual, 05/2010, A5E03264275A
8.5 Commissioning TM54F by means of STARTER/SCOUT