1.2.4
EN ISO 13849-1 (previously EN 954-1)
A qualitative analysis (to EN 954-1) is not sufficient for modern controllers due to their
technology. Among other things, EN 954-1 does not take into account time behavior (e.g.
test interval and/or cyclic test, lifetime). This results in the probabilistic basis in EN ISO
13849-1 (probability of failure per unit time).
EN ISO 13849-1 is based on the known categories of EN 954-1. It now also takes into
account complete safety functions and all the devices required to execute these. With EN
ISO 13849-1, safety functions are investigated from a quantitative perspective going beyond
the qualitative basis of EN 954-1. Performance levels (PL), which are based on the
categories, are used. The following safety-related characteristic quantities are required for
devices/equipment:
● Category (structural requirement)
● PL: Performance level
● MTTF
● DC: Diagnostic coverage
● CCF:
The standard describes how the performance level (PL) is calculated for safety-related
components of the controller on the basis of designated architectures. For deviations from
this, EN ISO 13849-1 refers to EN 61508.
When combining several safety-related parts to form a complete system, the standard
explains how to determine the resulting PL.
Note
Since December 2008, EN ISO 13849-1 has been harmonized as part of the Machinery
Directive. EN 954-1 will continue to apply until 30.12.2011.
Safety Integrated
Function Manual, 05/2010, A5E03264275A
: Mean time to dangerous failure
d
Common cause failure
Typicals and regulations