Mitsubishi Electric MELSEC iQ-R Series User Manual page 153

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Logging cycle setting value
Set a cycle for storing the logging data.
For details on the logging function, refer to the following.
Page 40 Logging Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging cycle setting value
CH Logging cycle setting value (in Q
compatible mode)
■Setting range
The setting range varies depending on the setting in 'CH1 Logging cycle unit setting' (Un\G538).
CH1 Logging cycle unit setting (Un\G538)
ms (1)
s (2)
• Setting a value out of the above range causes a logging cycle setting value range error (error code: 1D1H). Logging
cannot be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2H) occurs. Logging cannot be performed.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
• Thermocouple input module: The default value is 240 for all the channels.
• RTD input module: The default value is 80 for all the channels.
CH1 Logging cycle unit setting
Set a cycle unit for storing the logging data.
For details on the logging function, refer to the following.
Page 40 Logging Function
Setting value
1
2
• Setting a value out of the above range causes a logging cycle setting value range error (error code: 1D1H). Logging
cannot be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2H) occurs. Logging cannot be performed.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging cycle unit setting
CH Logging cycle unit setting (in Q
compatible mode)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default is ms (1) for all the channels.
CH1
CH2
CH3
537
737
937
1032
1033
1034
Setting range
30 to 32767 (for the thermocouple input module)
10 to 32767 (for the RTD input module)
1 to 3600
Setting content
ms
s
CH1
CH2
CH3
538
738
938
1040
1041
1042
CH4
CH5
CH6
1137
1337
1537
1035
1036
1037
CH4
CH5
CH6
1138
1338
1538
1043
1044
1045
Appendix 3 Buffer Memory Areas
CH7
CH8
1737
1937
1038
1039
A
CH7
CH8
1738
1938
1046
1047
APPX
151