CH1 Scaling range lower limit value
Set a lower limit value for the range of the scale conversion.
For details on the scaling function, refer to the following.
Page 23 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling range lower limit value
CH Scaling range lower limit value (in Q
compatible mode)
■Setting range
The possible range is from -32768 to 32767 (-3276.8 to 3276.7). (can be set in a unit of 0.1)
A channel where the set values do not satisfy the condition "Scaling upper limit value  Scaling lower limit value" causes a
scaling setting range error (error code: 1A3H).
When 'CH1 Scaling enable/disable setting' (Un\G546) is set to Disable (1), the setting for 'CH1 Scaling lower limit value'
(Un\G550) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all the channels.
CH1 Scaling width upper limit value
Set an upper limit on the width of scale conversion.
For details on the scaling function, refer to the following.
Page 23 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling width upper limit value
CH Scaling width upper limit value (in Q
compatible mode)
■Setting range
The possible range is from -32768 to 32767.
A channel where the set values do not satisfy the condition "Scaling upper limit value  Scaling lower limit value" causes a
scaling setting range error (error code: 1A3H).
When 'CH1 Scaling enable/disable setting' (Un\G546) is set to Disable (1), the setting for 'CH1 Scaling width upper limit value'
(Un\G552) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all the channels.
CH1
CH2
CH3
550
750
950
62
64
66
CH1
CH2
CH3
552
752
952
79
81
83
CH4
CH5
CH6
1150
1350
1550
68
70
72
CH4
CH5
CH6
1152
1352
1552
85
87
89
Appendix 3 Buffer Memory Areas
CH7
CH8
1750
1950
74
76
A
CH7
CH8
1752
1952
91
93
APPX
157