Mitsubishi Electric MELSEC iQ-R Series User Manual page 86

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error name
190H
Range setting range error
191H
Averaging process
specification setting range
error
192H
Time average setting range
error
193H
Count average setting range
error
194H
Moving average setting
range error
195H
Primary delay filter constant
setting range error
1A0H
Scaling enable/disable
setting range error
1A3H
Scaling setting range error
1B0H
Alert output setting (Process
alarm) range error
3 TROUBLESHOOTING
84
3.4 List of Error Codes
Description and cause
■For the thermocouple input module
• A value out of the range is set in CH Range
setting (Thermocouple type).
• A value out of the range is set in CH Range
setting (Offset/gain setting).
■For the RTD input module
• A value out of the range is set in CH Range
setting (Resistance temperature detector type).
• A value out of the range is set in CH Range
setting (Offset/gain setting).
A value other than 0 to 4 is set in CH Averaging
process specification.
■For the thermocouple input module
When Time average is selected in CH Averaging
process specification, the following value is set in
CH Time average/Count average/Moving average/
Primary delay filter constant setting:
• A value other than 120 to 5000
• A value smaller than "4  Number of channels
used  Conversion speed" (ms)
■For the RTD input module
When Time average is selected in CH Averaging
process specification, the following value is set in
CH Time average/Count average/Moving average/
Primary delay filter constant setting:
• A value other than 40 to 5000
• A value smaller than "4  Number of channels
used  Conversion speed" (ms)
When Count average is selected in CH Averaging
process specification, a value other than 4 to 500 is
set in CH Time average/Count average/Moving
average/Primary delay filter constant setting.
When Moving average is selected in CH
Averaging process specification, a value other than
2 to 200 is set in CH Time average/Count average/
Moving average/Primary delay filter constant setting.
When Primary delay filter is selected in CH
Averaging process specification, a value other than
1 to 500 is set in CH Time average/Count average/
Moving average/Primary delay filter constant setting.
A value other than 0 and 1 is set in CH Scaling
enable/disable setting.
The values satisfying the following condition are set
in CH Scaling range lower limit value and CH
Scaling range upper limit value.
Scaling range lower limit value = Scaling range
upper limit value
The values satisfying the following condition are set
in CH Scaling width lower limit value and CH
Scaling width upper limit value.
Scaling width lower limit value = Scaling width upper
limit value
A value other than 0 and 1 is set in CH Alert output
setting (Process alarm).
Action
■For the thermocouple input module
• Set a value of 0 to 7 in CH Range setting
(Thermocouple type).
• Set 0 or 1 in CH Range setting (Offset/gain
setting).
■For the RTD input module
• Set a value of 0 to 5, 8, or 9 in CH Range setting
(Resistance temperature detector type).
• Set 0 or 1 in CH Range setting (Offset/gain
setting).
Set a value of 0 to 4 in CH Averaging process
specification.
■For the thermocouple input module
Set the following value in CH Time average/Count
average/Moving average/Primary delay filter
constant setting:
• 120 to 5000
• A value equal to or greater than "4  Number of
channels used  Conversion speed" (ms)
■For the RTD input module
Set the following value in CH Time average/Count
average/Moving average/Primary delay filter
constant setting:
• 40 to 5000
• A value equal to or greater than "4  Number of
channels used  Conversion speed" (ms)
Set a value of 4 to 500 in CH Time average/Count
average/Moving average/Primary delay filter
constant setting.
Set a value of 2 to 200 in CH Time average/Count
average/Moving average/Primary delay filter
constant setting.
Set a value of 1 to 500 in CH Time average/Count
average/Moving average/Primary delay filter
constant setting.
Set 0 or 1 in CH Scaling enable/disable setting.
Set the values satisfying the following condition in
CH Scaling range lower limit value and CH
Scaling range upper limit value.
Scaling range lower limit value  Scaling range
upper limit value
Set the values satisfying the following condition in
CH Scaling width lower limit value and CH
Scaling width upper limit value.
Scaling width lower limit value  Scaling width upper
limit value
Set 0 or 1 in CH Alert output setting (Process
alarm).