Error code
Error name
190H
Range setting range error
191H
Averaging process
specification setting range
error
192H
Time average setting range
error
193H
Count average setting range
error
194H
Moving average setting
range error
195H
Primary delay filter constant
setting range error
1A0H
Scaling enable/disable
setting range error
1A3H
Scaling setting range error
1B0H
Alert output setting (Process
alarm) range error
3 TROUBLESHOOTING
84
3.4 List of Error Codes
Description and cause
■For the thermocouple input module
• A value out of the range is set in CH Range
setting (Thermocouple type).
• A value out of the range is set in CH Range
setting (Offset/gain setting).
■For the RTD input module
• A value out of the range is set in CH Range
setting (Resistance temperature detector type).
• A value out of the range is set in CH Range
setting (Offset/gain setting).
A value other than 0 to 4 is set in CH Averaging
process specification.
■For the thermocouple input module
When Time average is selected in CH Averaging
process specification, the following value is set in
CH Time average/Count average/Moving average/
Primary delay filter constant setting:
• A value other than 120 to 5000
• A value smaller than "4 Number of channels
used Conversion speed" (ms)
■For the RTD input module
When Time average is selected in CH Averaging
process specification, the following value is set in
CH Time average/Count average/Moving average/
Primary delay filter constant setting:
• A value other than 40 to 5000
• A value smaller than "4 Number of channels
used Conversion speed" (ms)
When Count average is selected in CH Averaging
process specification, a value other than 4 to 500 is
set in CH Time average/Count average/Moving
average/Primary delay filter constant setting.
When Moving average is selected in CH
Averaging process specification, a value other than
2 to 200 is set in CH Time average/Count average/
Moving average/Primary delay filter constant setting.
When Primary delay filter is selected in CH
Averaging process specification, a value other than
1 to 500 is set in CH Time average/Count average/
Moving average/Primary delay filter constant setting.
A value other than 0 and 1 is set in CH Scaling
enable/disable setting.
The values satisfying the following condition are set
in CH Scaling range lower limit value and CH
Scaling range upper limit value.
Scaling range lower limit value = Scaling range
upper limit value
The values satisfying the following condition are set
in CH Scaling width lower limit value and CH
Scaling width upper limit value.
Scaling width lower limit value = Scaling width upper
limit value
A value other than 0 and 1 is set in CH Alert output
setting (Process alarm).
Action
■For the thermocouple input module
• Set a value of 0 to 7 in CH Range setting
(Thermocouple type).
• Set 0 or 1 in CH Range setting (Offset/gain
setting).
■For the RTD input module
• Set a value of 0 to 5, 8, or 9 in CH Range setting
(Resistance temperature detector type).
• Set 0 or 1 in CH Range setting (Offset/gain
setting).
Set a value of 0 to 4 in CH Averaging process
specification.
■For the thermocouple input module
Set the following value in CH Time average/Count
average/Moving average/Primary delay filter
constant setting:
• 120 to 5000
• A value equal to or greater than "4 Number of
channels used Conversion speed" (ms)
■For the RTD input module
Set the following value in CH Time average/Count
average/Moving average/Primary delay filter
constant setting:
• 40 to 5000
• A value equal to or greater than "4 Number of
channels used Conversion speed" (ms)
Set a value of 4 to 500 in CH Time average/Count
average/Moving average/Primary delay filter
constant setting.
Set a value of 2 to 200 in CH Time average/Count
average/Moving average/Primary delay filter
constant setting.
Set a value of 1 to 500 in CH Time average/Count
average/Moving average/Primary delay filter
constant setting.
Set 0 or 1 in CH Scaling enable/disable setting.
Set the values satisfying the following condition in
CH Scaling range lower limit value and CH
Scaling range upper limit value.
Scaling range lower limit value Scaling range
upper limit value
Set the values satisfying the following condition in
CH Scaling width lower limit value and CH
Scaling width upper limit value.
Scaling width lower limit value Scaling width upper
limit value
Set 0 or 1 in CH Alert output setting (Process
alarm).