Mitsubishi Electric MELSEC iQ-R Series User Manual page 142

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• Set a primary delay filter constant for the primary delay filter. The value of the time constant (ms) is the
product of the primary delay filter constant and the sampling cycle.
• Since the default value is 0, change the setting value according to the processing method.
• The setting for this area is ignored in the channel where Sampling processing (0) is set to 'CH1 Averaging
process specification' (Un\G501).
CH1 Alert output setting (Process alarm)
Set whether to enable or disable the alert output of the process alarm.
For details on the alert output function, refer to the following.
Page 27 Alert Output Function
Setting value
0
1
Setting a value other than the above causes an alert output setting (Process alarm) range error (error code: 1B0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alert output setting (Process alarm)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (1) for all the channels.
APPX
140
Appendix 3 Buffer Memory Areas
Setting content
Enable
Disable
CH1
CH2
CH3
512
712
912
CH4
CH5
CH6
1112
1312
1512
CH7
CH8
1712
1912