Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting procedure
■For the thermocouple input module
1.
When using the thermocouple input module, set "Thermocouple type setting".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Thermocouple
type selection function]
2.
Set "Offset/gain setting" to "Factory default setting" or "User range setting".
■For the RTD input module
1.
When using the RTD input module, set "RTD type setting".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [RTD type
selection function]
2.
Set "Offset/gain setting" to "Factory default setting" or "User range setting".
Precautions
The input range cannot be changed for channels where conversion is disabled. To change the input range, set "Conversion
enable/disable setting" to "Conversion enable".
1 FUNCTIONS
1.2 Input Range Setting Function
1
17