Mitsubishi Electric MELSEC iQ-R Series User Manual page 141

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Averaging process specification [Q compatible mode]
For Q compatible mode, set which processing to use, sampling processing, averaging processing, or filter processing.
b15
...
b12 b11
...
(1)
CH4
CH3
b15
...
b12 b11
...
(2)
CH8
CH7
(1) Averaging process specification (Un\G24) (setting range CH1 to CH4)
(2) Averaging process specification (Un\G25) (setting range CH5 to CH8)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Averaging process setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Sampling processing (0) for all the channels.
CH1 Time average/Count average/Moving average/Primary delay filter constant setting
Configure the time (for averaging), count (for averaging), moving average count, and primary delay filter constant for each
channel where the averaging processing is specified.
The following table lists the setting ranges.
Setting value
Thermocouple input module: 120 to 5000 (ms)
RTD input module: 40 to 5000 (ms)
4 to 500 (times)
2 to 200 (times)
1 to 500 (times)
Setting a value other than the above causes either of the following: a time average setting range error (error code: 192H),
count average setting range error (error code: 193H), moving average setting range error (error code: 194H), or primary
delay filter constant setting range error (error code: 195H). The temperature conversion processing is performed with the
settings before the occurrence of the error.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Time average/Count average/Moving
average/Primary delay filter constant setting
CH Time average/Count average/Moving
average/Primary delay filter constant setting (in
Q compatible mode)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all the channels.
b8 b7
...
b4
b3
...
CH2
CH1
b8 b7
...
b4
b3
...
CH6
CH5
CH1
CH2
CH3
24
CH1
CH2
CH3
502
702
902
1
2
3
b0
b0
CH4
CH5
25
Setting content
Time average
Count average
Moving average
Primary delay filter constant
CH4
CH5
1102
1302
4
5
Appendix 3 Buffer Memory Areas
CH6
CH7
CH8
CH6
CH7
CH8
1502
1702
1902
6
7
8
APPX
A
139

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60td8-gR60rd8-g

Table of Contents