Judgment of rate alarm
A change rate is judged with the following formulae every rate alarm alert detection cycle.
• For alert outputting of rate alarm upper limit
Measured temperature value of this time - Measured temperature value of previous detection cycle Rate alarm upper limit
value
• For alert outputting of rate alarm lower limit
Measured temperature value of this time - Measured temperature value of previous detection cycle Rate alarm lower limit
value
Ex.
Judgment of rate alarm for the thermocouple input module, with the following conditions
• Conversion enabled channel: CH1
• CH1 Range setting (Thermocouple type): K thermocouple
• CH1 Averaging process specification: Sampling processing
• Rate alarm alert detection cycle setting: 5 (times)
• CH1 Rate alarm upper limit value: 10000 (1000.0)
• CH1 Rate alarm lower limit value: 3200 (320.0)
A measured temperature value of this time is compared to the previous value (measured temperature value 150ms before),
every rate alarm alert detection cycle of 150ms (30ms 5). From the comparison, whether the increase in the measured
temperature value is 10000 (1000.0) or more, or 3200 (320.0) or less is judged.
Detection target for outputting an alert
'CH1 Measured temperature value' (Un\G400) is a target for outputting an alert. The target is the same for when the scaling
function is enabled.