Code
P5-01
P5-02
P1-01
P2-01
P2-02
P2-03,
P2-04
P2-05,
P2-06
P3-01 ...
P3-06
P4-01
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Description
Activate hour counter
Activate demand values
Setting 0000 (default) deactivates password protection. Every other setting defines
the password for access to advanced functions.
Defines the function of output 1:
• OFF = Deactivated
• 1000 PUL ... 1 PUL = Output 1 functions as a pulse transmitter for active
energy counting. This selection defines the number of pulses transmitted for
each kWh.
• THR = Output 1 becomes an alarm threshold for the maximum or minimum
limit, depending on the values programmed in P2-03 and P2-05.
If P2-03 ≥ P2-05, the output is activated if the measurement defined by P2-02 is
higher than P2-03 and deactivated if its value is lower than P2-05 (maximum
limit with hysteresis).
If P2-03 < P2-05, the output is activated if the measurement defined by P2-02 is
lower than P2-03 and activated if its value is lower than P2-05 (minimum limit
with hysteresis).
Selects the measured variable for comparison with limit thresholds. You can find
more information on this in chapter Settable values for parameters P2.01, P3.01,
P4.01 (Page 40).
Limit threshold and delay for activation of the output.
Note: The measurements are updated every second. The inaccuracy of this delay lies
within the range from 0 to 1 second.
Limit threshold and delay for deactivation of the output.
Same function as P2-01 ... P2-06, but with reference to output 2.
Selects the function of the programmable input:
• OFF = Input deactivated.
• ON = Input activated (for general functions, such as hour counter enable).
• TAR = Selects the energy tariff (T1/T2).
• CLr Part = Clears the partial energy meters
• CLr Hr = Clears the hour counter.
• CLr dE = Clears the max. demand values.
3.4 Three-phase devices 80 A
Default
Range
OFF
•
OFF
•
ON
•
THR1
•
THR2
•
INP
OFF
•
OFF
•
ON
Description
39