P05 Hour counter
P05.01
P05.02
P05.03
P05.04
P05.05
P05.06
P05.07
P05.08
P05.09
P05.01 The hour counters are deactivated when OFF is set. The hour counters do not ap-
P05.02,
P05.04,
P05.06,
P05.08
P05.03,
P05.05,
P05.07,
P05.09
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Activate total hour
counter
Activate partial hour
counter 1
Hour counter
channel number 1
Activate partial hour
counter 2
Hour counter
channel number 2
Activate partial hour
counter 3
Hour counter
channel number 3
Activate partial hour
counter 4
Hour counter
channel number 4
pear on the display.
• The partial hour counter (1, 2, 3, or 4) cannot be incremented when OFF is set.
• When ON is set, the partial hour counter is incremented when the energy meter
is exporting energy.
• If the partial hour counter is linked to one of the internal variables (LIMn), the
partial hour counter is only incremented if this condition is true.
Channel number (n) of an internal variable which was used in the previous parame-
ter.
Example:
If the partial hour counter needs to count the time while one measurement is above
a particular threshold that was defined by LIM3, program LIMx in the previous pa-
rameter and enter "3" in this parameter.
Unit
Default
–
ON
1
ON
1
ON
1
ON
1
Description
3.5 Three-phase devices 5 A
Range
OFF
ON
•
OFF
•
ON
•
LIMx
1 ... 4
•
OFF
•
ON
•
LIMx
1 ... 4
•
OFF
•
ON
•
LIMx
1 ... 4
•
OFF
•
ON
•
LIMx
1 ... 4