Power values
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
Hex
Decimal
ters
0812
2066
2
Range limit
0A12
2578
2
Energy counters
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
Hex
Decimal
ters
1A20
6688
2
1A22
6690
2
1A24
6692
2
1A26
6694
2
1A28
6696
2
1A2A
6698
2
1A2C
6700
2
1A2E
6702
2
Operating hours counter
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
Hex
Decimal
ters
1E00
7680
2
1E02
7682
2
Status
Modbus measured variables with the function codes 03 and 04
Address
Number
Register
Hex
Decimal
2210
8720
1
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Format
Access
Unit
INT32
R
W
INT32
R
W
Format
Access
Unit
UINT32
R
Wh
–
–
–
UINT32
R
varh
–
–
–
–
–
–
UINT32
R
Wh
–
–
–
UINT32
R
varh
Format
Access
Unit
UINT32
R
s
UINT32
R
s
Format
Access
Unit
UINT
R
–
6.4 Modbus address register
Factor
Measured variable
0.1
Average active power
(15m demand)
0.1
Max. average active power
(max demand)
Factor
Measured variable
1.0
Total active energy
–
–
1.0
Total reactive energy
––
–
–
–
1.0
Partial active energy
–
–
1.0
Partial reactive energy
Factor
Measured variable
1.0
Operating hours counter
1.0
Partial operating hours counter
Factor
Measured variable
–
Status of the programmable threshold
Commissioning
83