Monitor Display Selection For Terminals Fm And Am - Mitsubishi Electric 800 Series Instruction Manual (Function

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

13.3

Monitor display selection for terminals FM and AM

For the standard model, monitored values are output in either of the following: analog voltage (terminal AM) in the AM type
inverters (FR-E800-4 and FR-E800-5) or pulse train (terminal FM) in the FM type inverter (FR-E800-1).
The signal (monitor item) to be output to terminal FM and terminal AM can be selected.
Pr.
Name
54
FM terminal function selection
*2
M300
158
AM terminal function selection
*3
M301
55
Frequency monitoring reference
*4
M040
56
Current monitoring reference
*4
M041
866
Torque monitoring reference
M042
290
Monitor negative output
M044
selection
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
*2
The setting is available only for the FR-E800-1.
*3
The setting is available only for the FR-E800-4 and FR-E800-5.
*4
For the Ethernet model and the safety communication model, the setting is available only when the plug-in option (FR-A8AY) is installed.
 Monitor description list (Pr.54, Pr.158)
• Set the type of monitor to be output through terminal FM (pulse train output) in Pr.54 FM terminal function selection.
Terminal FM is provided in the FM type inverter.
• Set Pr.158 AM terminal function selection for monitoring via terminal AM (analog voltage output). Negative signals can
be output via terminal AM (in the range of -10 to +10 VDC). The circle in the Negative output column indicates that the
output of negative signals is available via terminal AM. (To enable or disable the negative output, refer to
Terminal AM is provided in the AM type inverter.
• Refer to the following table and select the item to be monitored. (Refer to
Increment and
Monitor item
Output frequency
0.01 Hz
*1
0.01 A
Output current
Output voltage
0.1 V
Frequency setting value
0.01 Hz
*1
Initial value
Gr.1
Gr.2
1 (output
frequency)
60 Hz
50 Hz
Inverter rated
current
150%
0
Pr.54 (FM),
Pr.158 (AM)
unit
setting
*3
1
2
3
*3
5
Setting range
1 to 3, 5 to 14, 17, 18,
21, 24, 32, 33, 50, 52,
Select the item monitored via terminal FM.
53, 61, 62, 65, 67, 70,
97
1 to 3, 5 to 14, 17, 18,
21, 24, 32, 33, 50, 52 to
Select the item monitored via terminal AM.
54, 61, 62, 65, 67, 70,
91, 97
Set the full-scale value when the output
0 to 590 Hz
frequency monitor value is output via terminal
FM or AM.
Set the full-scale value when the output
0 to 500 A
current monitor value is output via terminal FM
or AM.
Set the full-scale value when the torque
0% to 400%
monitor value is output via terminal FM or AM.
Set the availability of negative values for
indication via terminal AM, via communication,
0, 1, 4, 5, 8, 9, 12, 13
and via terminal AM0 (of the FR-A8AY). (Refer
to
page
page
54).
page 311
for the list of monitor items.)
Terminal FM/AM
Negative
full-scale value
output
Pr.55 or the value
converted with the
Pr.37 or Pr.81
(Pr.454) value from
Pr.55.
Pr.56
200 V class: 400 V,
400 V class: 800 V,
575 V class: 1000 V
Pr.55 or the value
converted with the
Pr.37 or Pr.81
(Pr.454) value from
Pr.55.
13. (M) Item and Output Signal for Monitoring
13.3 Monitor display selection for terminals FM and AM
Description
318.)
page
Remarks
11
12
13
14
15
16
17
18
19
20
310.)
319