Pr.178 to Pr.184 (Input terminal function
2.7.2
Giving a start command from the operation panel
for JOG operation
• JOG operation is performed while the RUN key on the operation panel is pressed.
The following shows the procedure to operate at 5 Hz.
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Press the PU/EXT key twice to choose the PUJOG operation mode. The display shows "JOG", and the PU LED is
ON.
3.
Start → acceleration → constant speed
Hold down the RUN key. The frequency value on the monitor increases according to the setting of Pr.16 Jog
acceleration/deceleration time, and "5.00" (5.00 Hz) appears on the monitor.
4.
Deceleration → stop
Release the RUN key. The frequency value on the monitor decreases according to the setting of Pr.16 Jog
acceleration/deceleration time, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating.
NOTE
• To change the frequency, change the setting of Pr.15 Jog frequency (initial value: 5 Hz).
• To change the acceleration/deceleration time, change the setting of Pr.16 Jog acceleration/deceleration time (initial value:
0.5 seconds).
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration
50
2. Basic Operation
2.7 Basic operation procedure (JOG operation)
selection)page 368
Operation panel
timepage 271