16.2

Stop-on-contact control

Magnetic flux Sensorless
Magnetic flux
Magnetic flux
Sensorless
Sensorless
To ensure accurate positioning at the upper limit, etc. of a lift, stop-on-contact control causes the mechanical brake to close
while the motor creates a holding torque to keep the load in contact with a mechanical stopper, etc.
This function suppresses vibration that is likely to occur when the load is stopped upon contact in lift applications, thereby
ensuring reliable and highly accurate positioning stop.
<Without stop-on-contact control>
Vibration
Complete stop
Lift
Pr.
Name
6
Multi-speed setting (low
D303
speed)
22
Stall prevention operation level 150%
H500
48
Second stall prevention
H600
operation level
270
Stop-on-contact control
A200
selection
Stop-on contact excitation
275
current low-speed scaling
A205
factor
276
PWM carrier frequency at stop-
A206
on contact
 Connection and operation example
•Sink logic
MCCB
Power
supply
Forward rotation command
High-speed operation command
Middle-speed operation command
Stop-on contact selection 0
Stop-on contact selection 1
∗ The input terminal used differs according to the Pr.180 to Pr.189 settings.
<With stop-on-contact control>
Lift
Setting
Initial value
range
10 Hz
0 to 590 Hz
0% to 400%
0% to 400%,
9999
9999
0
0
1
11
0% to 300%
9999
9999
0 to 9
9999
9999
MC
U
R/L1
V
S/L2
W
T/L3
STF
RH∗
RM∗
RL∗
RT∗
SD
Description
Set the output frequency for stop-on-contact control.
Set the stall prevention operation level for stop-on-contact control.
The smaller value set in either Pr.22 or Pr.48 has priority.
Normal operation
Stop-on-contact control
Stop-on-contact control (E.OLT is invalid)
Set the force (holding torque) for stop-on-contact control.
Normally, set the scaling factor between 130% to 180%.
Not compensated.
Set a PWM carrier frequency for stop-on-contact control.
For Real sensorless vector control, the carrier frequency is always
2 kHz when the setting value is "0 to 5" and always 6 kHz when
the setting value is "6 to 9". (Valid at the output frequency of 3 Hz
or less.)
As set in Pr.72 PWM frequency selection.
Normal mode
Pr.4
Mechanical
Pr.5
brake
Pr.6
0
(a)
Motor
RH
ON
RM
OFF
RL
OFF
RT
OFF
∗ Goes into stop-on-contact control mode when
both RL and RT switch on.
RL and RT may be switched on in any order
with any time difference
(a): Acceleration time(Pr.7)
(b): Deceleration time(Pr.8)
(c): Second deceleration time(Pr.44/Pr.45)
Stop-on contact
control mode
Time
(b)
(c)
ON
ON
ON
16. (A) Application Parameters
16.2 Stop-on-contact control
11
12
13
14
15
16
17
18
19
20