ABB ACS560 Quick Installation And Start-Up Manual page 127

Standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
1 - Maximum current limit too low
2 - Maximum speed limit or calculated field
weakening point too low
3 - Maximum torque limit too low
4 - Current measurement calibration not finished
within reasonable time
5...8 - Internal error
9 - (Asynchronous motors only). Acceleration
not finished within reasonable time.
A - (Asynchronous motors only) .Deceleration
not finished within reasonable time.
FF63
STO diagnostics fail-
ure.
FF81
FB A force trip
FF8E
EFB force trip
Cause
B - (Asynchronous motors only) Speed dropped
to zero during ID run.
C - (Permanent magnet motors only). First accel-
eration did not finish within reasonable time.
D - (Permanent magnet motors only). Second
acceleration did not finish within reasonable time.
E...10 - Internal error
11 - (Synchronous reluctance motors only).
Pulse test error.
12 - Motor too large for advanced standstill ID
run.
13 - (Asynchronous motors only). Motor data
error.
SW internal malfunction.
A fault trip command through
fieldbus adapter A.
A fault trip command through
embedded fieldbus interface.
Diagnostics 127
What to do
Reboot the control unit (using parameter
96.08 Control board boot or by cycling
power.
Check the fault information provided by the
PLC.
Check the fault information provided by the
PLC.