Typical Power Cable Sizes; Dimensions, Weights And Free Space Requirements - ABB ACS560 Quick Installation And Start-Up Manual

Standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Typical power cable sizes

Drive type
Frame size
ACS560
3-phase U
= 400 V (380...480 V)
N
02A6-4
R0
03A3-4
R0
04A0-4
R0
05A6-4
R0
07A2-4
R0
09A4-4
R0
12A6-4
R1
017A-4
R2
025A-4
R2
033A-4
R3
039A-4
R3
046A-4
R3
062A-4
R4
073A-4
R4
088A-4
R5
106A-4
R5
145A-4
R6
169A-4
R7
206A-4
R7
246A-4
R8
293A-4
R8
1) The cable sizing is based on maximum parallel layout of 6 cables laid on a cable ladder side by side, ambient temperature
30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other conditions, size the
cables according to local safety regulations, appropriate input voltage and the load current of the drive.
2) Aluminum cables must not be used with frames R0...R4.
3) In the USA, aluminum cables must not be used.

Dimensions, weights and free space requirements

Frame
W
mm
R0
73
R1
97
R2
172
R3
203
R4
203
1)
IEC
Cu cable type
AI cable type
2
mm
mm
3 × 1.5 + 1.5
-
3 × 1.5 + 1.5
-
3 × 1.5 + 1.5
-
3 × 1.5 + 1.5
-
3 × 1.5 + 1.5
-
3 × 2.5 + 2.5
-
3 × 2.5 + 2.55
-
3 × 2.5 + 2.5
-
3 × 6 + 6
-
3 × 10 + 10
-
3 × 10 + 10
-
3 × 16 + 16
-
3 × 25 + 16
3 × 35
3 × 35 + 16
3 × 50
3 × 35 + 16
3 × 70
3 × 50 + 25
3 × 70
3 × 95 + 50
3 × 120
3 × 120 + 70
3 × 150
3 × 150 + 70
3 × 240
2 × (3 × 70 + 35)
2 × (3 × 95)
2 × (3 × 95 + 50)
2 × (3 × 120)
Dimensions and weight
IP20
D
H1
mm
mm
207
223
207
223
207
220
229
490
257
636
Technical data 103
US
2)
Cu cable type
AI cable type
2
AWG/kcmil
16
16
16
16
16
14
14
14
10
8
8
6
4
2
2
1/0
3/0
250 MCM
300 MCM
2 × 2/0
2 × 3/0
H2
mm
x
x
x
x
x
3)
AWG/kcmil
-
-
-
EN
-
-
HI
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Weight
kg
1.6
1.9
2.9
14.9
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents