12.6 Device Function
Recorder Size in MB
Size of the physical memory area in Mbytes for each recorder.
Recording Depth
Recording time in days (d) and hours (h) - it is calculated from the recording times, the
number of active channels and the configuration components
Total Memory
Total memory capacity of the parameterized recorders.
Avbl. Memory
Memory that can be allocated freely.
Note
Changes in the memory allocation will delete all data recordings in the device. No warning is
given during parameterization.
OSCOP P monitors the allocation of memory space.
If the memory capacity is not sufficient for a continuous mean value recorder and the overall
memory capacity of the device has been reached, please proceed as follows:
Reduce the memory capacity of another recorder.
Note
Please note that unchecking a checkbox does not automatically deallocate memory space.
Increase the memory capacity of the continuous mean value recorder by the memory space
that has been deallocated beforehand.
Allocate a memory area of at least 1.5 MByte to each recorder.
For system data 100 MByte are reserved. This has to be considered for the hard disk size.
OSCOP P considers this fact automatically when calculating the available memory.