14.2.4

Connecting Cables (Power Supply, Signals, Measurement Circuits)

The following table shows the connected loads of the connection modules and examples for the
corresponding cable types. Every connection point of the connection modules is available both
as a screw terminal and a plug-in contact (crimp contact).
Table 14-1
Crimp contacts
1
0.5 mm
1.5 mm
2
1.5 mm
Stripping length:
5 mm
Tools:
Comp. Harting FC3, no. 09990000077
Note
The connection and assignment diagrams of the individual modules are shown in detail in
Chapter 15.
Detailed technical information, for example, regarding the switching capacity of the signal
outputs can be found in Chapter 16.
If the connection wires are designed as finely-stranded wires, the wire ends must be flattened
with a wire end ferrule. Screw connections are to be preferred; plug-in connections require
special tools and are allowed for line wiring only if reliable strain relief is provided.
Screw terminals can be used without wire end ferrule. Terminal pins must not be used. Make
sure the stripping length of the conductors is sufficient: approx. 15 mm, however, not less than
10 mm.
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
for plug-in module III, Comp. Weidmüller, no. 162553
2
2
to 1 mm
for plug-in module III, Comp. Weidmüller, no. 162551
2
2
to 2.5 mm
for plug-in module I, Comp. Grote u. Hartmann,
2
2
to 2.5 mm
no. 26457.331.410