Siemens SIMEAS R-PMU Manual page 285

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

Log No. Type
Class
2313
0
OSCOP
2314
2
OSCOP
2315
0
OSCOP
2316
1
OSCOP
2561
2
OSCOP
2562
0
OSCOP
2563
2
OSCOP
2564
1
OSCOP
2566
1
OSCOP
3120
2
SYNC
3121
2
SYNC
3122
0
SYNC
3123
1
SYNC
3124
0
SYNC
3125
0
SYNC
3126
0
SYNC
3127
0
SYNC
3128
0
SYNC
3129
0
SYNC
3184
2
SYSTEM
3185
1
SYSTEM
3186
1
SYSTEM
3187
1
SYNC
3188
1
SYNC
3189
2
SYNC
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Description
Fault during change to normal mode by
OSCOP P
Lock mode activated by OSCOP
Fault during change to lock mode by
OSCOP P
OSCOP P communication request via V20/
V30 protocol rejected
Logon service mode
Unable to logon for service mode
Logoff service mode
Logoff service mode with device reboot
Incorrect password
External synchronization pulse OK
Device synchronized
Synchronization fault: Pulse loss
Synchronization: Non-critical pulse failure
Synchronization fault: Too many non-critical
pulse losses
Synchronization fault: Pulse width invalid
Synchronization fault: Pulse distance invalid Pulse gap must be 1 s for GPS/DCF77 or
Synchronization fault: DCF77 minute mark
not found
DCF77 synchronization parity fault:
Synchronization fault: Non-supported Sync-
Box 7KE6000-8H* connected
DCF77 synchronization-supported
Synchronization fault: Manual time setting
rejected
Manual time setting rejected, minimum
distance not observed
Leap second announcement received
Leap second
System time zone changed
3 System Messages
Comment
Hotline
-
Hotline
Make sure to use OSCOP P, version 6.60
or higher and set device type
„SIMEAS R-PMU".
Switching from normal mode to service
mode; possible reason: Firmware update
rejected, parameter or password change
rejected
Hotline
-
Switching from normal mode to service
mode; possible reason: Deleting fault
records via OSCOP P, firmware update or
parameter changes
-
-
-
Synchronization signal lost. Check the clock
incl. antenna, antenna cable and the
synchronization signal cable.
Synchronization signal lost for a short time.
Check the clock incl. antenna, antenna
cable and the synchronization signal cable if
this error occurs repeatedly.
Synchronization signal lost for a short time
several times. Check the clock incl.
antenna, antenna cable and the
synchronization signal cable.
Pulse width of the synchronization signal
does not meet the specification. Check
parameterization of clock master.
60 s for minute pulse. Check
parameterization of clock master.
No valid DCF77 signal detected. Check
parameterization of clock master.
Check clock master and synchronization
signal cable; no valid DCF77 signal
detected.
The Sync-Box is supported as of SIMEAS
R-PMU firmware V40.01.
-
Time setting via OSCOP P is not allowed if
SIMEAS R-PMU is synchronized via GPS
signal.
Time gap between two time setting
commands must be at least 4 hours.
-
-
Device time zone was changed due to a
new parameterization or a firmware
upgrade.
285