Siemens SIMEAS R-PMU Manual page 248

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

16
16.1 Technical Data of the SIMEAS R-PMU
Voltage ranges
depending on the configuration
Binary inputs (CPU)
Control inputs
Input 1
Input 2
Input 3
Input 4
Voltage ranges
depending on the configuration
248
Input voltage
DC 24 V
DC 48 V to DC 60 V
DC 110 V to DC 125 V
DC 220 V to DC 250 V
Input current 1 mA
Input voltage
DC 24 V
DC 48 V to DC 60 V
DC 110 V to DC 125 V
DC 220 V to DC 250 V
Electrical isolation up to 2.2 kV, 50 Hz.
All binary DAU inputs are bipolar.
4
Time synchronization input for
connection to a GPS timer, a Sync-Box or a
station clock with minute pulse
24 V to 60 V, filter time >2 µs
>110 V, filter time <5 µs
External start, filter time 50 ms
External reset, filter time 50 ms
External group alarm, filter time 50 ms
Input
voltage
DC 24 V
DC 48 V to DC 60 V
DC 110 V to DC 125 V
DC 220 V to DC 250 V
Input current 1 mA
Input voltage
DC 24 V
DC 48 V to DC 60 V
DC 110 V to DC 125 V
DC 220 V to DC 250 V
Electrical isolation up to 2.2 kV, 50 Hz.
Input 1 of the CPU is unipolar, all other inputs are bipolar.
Digital Fault Recorder, SIMEAS R-PMU, Manual
L level
H level
7 V
18 V
14 V
36 V
28 V
75 V
56 V
165 V
Overload
DC 28.8 V
DC 72 V
DC 150 V
DC 300 V
L level
H level
7 V
18 V
14 V
36 V
28 V
75 V
56 V
165 V
Overload
DC 28.8 V
DC 72 V
DC 150 V
DC 300 V
E50417-H1076-C360-A5, Release 10.2012