Com 1 Interface; Serial Direct Connection - Siemens SIMEAS R-PMU Manual

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

10.4

COM 1 Interface

10.4.1

Serial Direct Connection

Use the 9-pin RS232 connection at the rear panel of the SIMEAS R-PMU for the serial
transmission of parameters and measured data. This serial interface can be used to set variable
baud rates.
Baud rate:
Data bits:
Stop bit:
Parity:
For communication between the SIMEAS R-PMU and PC/notebook or PDC, the data line must
be connected both to the data interface at the rear panel of the SIMEAS R-PMU and to the
corresponding COM port of the evaluation PC/DAKON or the PDC.
Note
Note that while using the serial connection (null modem) for transferring PMU data to the
PDC a concurrent communication to OSCOP P (Evaluation PC/DAKON) is not possible.
For null modem communication to the PDC, the PPP protocol is used (see
section 12.14.2).
Then set the corresponding interface parameters in the Parameterize PC module of the
OSCOP P software.
SIMEAS R-PMU
COM S
Wartungsschnittstelle
Frontseite
Figure 10-7 Serial data transmission (data interface)
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
9,600 bit/s to 115,200 bit/s
8
1
none
SIMEAS R-PMU
COM 1 data interface
Rückseite
Null modem cable, SIMEAS R-PMU -
evaluation PC, DAKON or PDC
10
10.4 COM 1 Interface
Evaluation PC
DAKON
PDC
125