13.2

Operator and Error Messages

13.2.1

General

The SIMEAS R-PMU records operator and error messages in different ways:
Recorded in the log recorder: The log entries can be read out and evaluated using OSCOP P.
Signaling via signal contacts (CPU relay contacts)
Display via LEDs at the control panel
Device state (see chapter 12.1)
Light-emitting diodes (LEDs)
There are 21 LEDs at the control panel:
LED 1 to 8 (red): Fault displays
LED 9 to 16 (green): Status information
LED 17 to 21 (yellow): Displaying general device messages.
Note
LEDs 1 to 16 can be parameterized freely. Up to five messages can be assigned to each LED.
If a message is provided, the LED that has been parameterized for this message will light up
(OR link).
LEDs 17 to 21 cannot be parameterized, they are permanently allocated.
Table 13-1 shows the allocation of LEDs 1 to 8 at delivery and describes the meaning of the
individual error messages.
Table 13-1
Error messages via LEDs
LED no.
1
DAU error
2
CPU error
3
Printer error
4
Data error
5
Synchronization error
6
PC not available
7
Temperature error
8
In reserve
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Message
13.2 Operator and Error Messages
Definition
DAU booting error or DAU failure (self-monitoring)
Error during reading or writing of the flash disk,
internal recorder fault, malfunction of the
communication processor
Malfunction of the local printer
Possible cause: paper tray empty, paper jam,
printer not ready or printer connection malfunction
DAU data consistency error or time-out during
DAU transmission
Synchronization signal failed or faulty
Evaluation PC or DAKON not available in call-
back mode
Operating temperature outside permissible
temperature range of -5 °C to +55 °C exceeded or
not reached
13
177