Surge
Power supply, control and
communications lines
Damped oscillation
Damped oscillation
Voltage dips and
short interruptions
Voltage fluctuations
AC/DC power supply unit
Voltage interruptions
AC power supply unit
Voltage dips
AC power supply unit
Interference emission
Interference field strength
Radio interference voltage
Harmonics
AC supply voltage
AC power supply unit
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1 Technical Data of the SIMEAS R-PMU
IEC 61000-4-5
extended as per customer requirements
Common mode 4 kV,
Differential mode 2 kV (extended 4 kV)
IEC 61000-4-18; EN 61000-4-18
Test level 3,
Common mode 2.5 kV
Differential mode 1 kV
Repetition rate 100 kHz and 1 MHz
IEC 61000-4-11; EN 61000-4-11
IEC 60255-11
Short interruption 100 % to 0 % for 50 ms
Short interruption 100 % to 50 % for 100 ms
IEC 61000-4-11; EN 61000-4-11
to 80 %, 120 % permanently,
to 40 %, dynamic 2 s, operation 2 s
to 0 %, dynamic 2 s, operation 1 s
IEC 61000-4-11; EN 61000-4-11
to 0 % for 5 s with 50 Hz / 60 Hz ±5 %
switch OFF and automatic restart
IEC 61000-4-11; EN 61000-4-11
to 0 % for 10 ms
to 40 % for 100 ms
to 70 % for 200 ms with 50 Hz / 60 Hz ±5 %
Function not affected
IEC/EN 61000-6-4
EN55011/CISPR11
Class A
EN55011/CISPR11
Class A
IEC 61000-3-2; EN 61000-3-2
Class A
16