Analog And Binary Inputs And Outputs - Siemens SIMEAS R-PMU Manual

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

16.1.4 Analog and Binary Inputs and Outputs

Slot 2
(ZE 8/16, one DAU)
Slots 2 to 5
(ZE 32/64, up to four DAUs)
Table 16-2
VCDAU
8 analog (4 current/4 voltage) and 16 binary
channels
VDAU
8 analog (8 voltage) and 16 binary channels
CDAU
8 analog (8 current) and 16 binary channels
DDAU
8 analog (8 current DC ±20 mA or
8 voltage DC ±1 V or DC ±10 V)
and 16 binary channels
BDAU
32 binary channels
Measured value processing
A/D converter: 16 bit, 64 times oversampling, 92 dB dynamic range
Table 16-3
Nominal
frequency
50 Hz
60 Hz
Table 16-4
Nominal
frequency
50 Hz
60 Hz
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Configuration options
VCDAU, VDAU and CDAU
Sampling
Frequency range
frequency
9,600 Hz
11,520 Hz
DDAU
Sampling
Frequency range
frequency
9,600 Hz
11,520 Hz
16.1 Technical Data of the SIMEAS R-PMU
Can be equipped as per Table 16-2
Can be equipped as per Table 16-2
Samples/cycle
25 Hz to 60 Hz
30 Hz to 70 Hz
Samples/cycle
0 Hz to 500 Hz
0 Hz to 500 Hz
16
192
192
192
192
245