4
4.4 Time Synchronization
4.4
Time Synchronization
Time synchronization is an important feature of the SIMEAS R-PMU and must be performed with
high precision. The phasor measurements in particular, require precise time stamping.
An exact time synchronization (<5 µs) of all devices is necessary, in order to ensure that the
records of fault recorders in different locations can be compared to each other.
Time synchronization of SIMEAS R-PMU devices can be implemented by using either:
DCF77 signal of a GPS clock
Modified DCF77 signal of a Sync-Box
Minute pulse
Note
The time synchronization function is parameterized using the parameter setting interface of
OSCOP P. The GPS clock must be parameterized separately (See Chapter 8).
28
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012