Beko BEKOMAT 16i CO Translation Of Original Installation And Operation Manual page 46

Table of Contents

Advertisement

BEKOMAT
®
16i CO
Illustration
For further information about fault indications during operation, see "15. Troubleshooting and fault repair / FAQ" on 
Page 72.
46 | 76
n = ∞
Original installation and operation manual
Description / explanation
Discharge procedure (TEST button pressed briefly)
The red ALARM LED is off.
The green VALVE LED is on during the discharge
procedure.
The green POWER LED is on.
Pre-alarm (TEST button pressed >1 minute and
<5 minutes)
The red ALARM LED flashes.
The green VALVE LED is on.
The green POWER LED is on.
Alarm (TEST button pressed >5 minutes)
The red ALARM LED is on.
The green VALVE LED is off.
The green POWER LED is on.
Alarm mode (condensate discharge is impaired)
The red ALARM LED flashes.
The green POWER LED is on.
The green VALVE LED is on when the solenoid valve is
cycling.
0 The solenoid valve is cycling every 4 minutes.
After the malfunction has been eliminated, the
BEKOMAT
automatically switches to normal operation.
®

Advertisement