SICHARGE UC Dispenser UL | Operating Instructions
CAUTION
Risk of stumbling or slipping
Keep the work area clean and tidy to prevent stumbling and slipping.
6.2

Connecting the power supply cable

To connect the SICHARGE UC dispenser to the SICHARGE UC charging station, connect the power supply
cable to the F1 and F2 fuses of the SICHARGE UC dispenser.
Grounding instructions
This unit is to be connected to a grounded, metal, permanent wiring system; or an equipment-grounding
conductor is to be run with circuit conductors and connected to an equipment-grounding terminal or lead
on battery charger. Connections to battery charger must comply with all local codes and ordinances.
Cable routing considerations
All circuits (incoming AC power wiring, DC wiring to dispensers, and communications wiring) should be
ran in separate conduit runs until reaching the cable gland plates.
Requirements
• You have opened the cabinet.
• You have inserted the power cable into the cabinet.
Connections of the power supply cable
The figure below shows the connection of the power supply cable. AC cables should be torqued
to a value of .5 to .6 Nm.:
54
a Terminal L1
s Terminal N
d Ground connection PE
f Loop through for daisy chain - L1, N, and PE - shown as dashed lines
Figure 6-1
Power supply cable connection