6.2

Connecting the power supply cable

To connect the SICHARGE UC dispenser to the SICHARGE UC charging station, connect the power supply
cable to the L1 and N fuses of the SICHARGE UC dispenser.
Grounding instructions
This unit is to be connected to a grounded, metal permanent wiring system; or an equipment-grounding
conductor is to be run with circuit conductors and connected to an equipment-grounding terminal or lead
on the SICHARGE UC charging station. Connections to the SICHARGE UC charging station must comply with
all local codes and ordinances.
Cable routing considerations
All circuits (incoming AC power wiring, DC wiring to dispensers and communications wiring) should be
ran in separate conduit runs until reaching the cable gland plates.
Requirements
• You have opened the cabinet.
• You have inserted the power cable into the cabinet.
Connections of the power supply cable
The figure below shows the connection of the power supply cable. AC cables should be torqued
to a value of 0.5 to 0.6 Nm.
54
a Terminal X23 (L1, 14 AWG - red)
s Terminal X24 (N, 14 AWG - red/white)
d Loop through for daisy chain - L1 and N - shown as dashed lines
Figure 6-1
Power supply cable connection