Siemens SICHARGE UC 150 UL Installation And Operation Manual page 36

Plug-in dispenser
Table of Contents

Advertisement

SICHARGE UC 150 UL Plug-in Dispenser | Installation and Operations Manual
Minimum clearances for wall mounting
For operation and maintenance and to ensure proper ventilation of the SICHARGE UC dispenser, you
must maintain the following minimum clearances (in mm):
Figure 4-4
Minimum clearances for wall mounting (front view)
Figure 4-5
Minimum clearances for wall mounting (top-down view)
Maximum allowable temperature at air inlet
The maximum permissible ambient temperature is 45 °C. When the ambient temperature exceeds 45 °C,
the charging process is interrupted. The SICHARGE UC dispenser must not be operated above the
maximum permissible ambient temperature.
Direction of air flow
Please note the direction of air flow when installing:
• Air-conditioning unit:
The supply air enters the SICHARGE UC dispenser from the back.
The exhaust air escapes through the louvers on both sides.
Avoid recirculating the exhaust air for cooling.
36