Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
26.6
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Form / Table of current consumption
Some national regulations require different forms / tables regarding
current consumption, to be filled-in. In such a case an ampere meter
shall be used to read a true value instead of a calculated current
consumption.
A tip: Turn off the main power source (230 V AC) and use e.g. a
"clamp current meter" on one of the wires between one of the batteries
and the Main board 5010, to read the true total current consumption.
An approx. value is displayed via menu H5/A4.
157