Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Quiscent state
Any detector
in alarm?
Yes
AP timer starts
IP timer starts
All detectors
normal?
No
Count down
IP time
remains?
Yes
No
Fire Alarm
in the C.I.E.
Figure 23. Alarm Acknowledgement Facility (AAF) flow chart.
During the AAF Process, an AAF alarm will be indicated in the c.i.e.
display ....
.... during the Acknowledgement Period (A Period):
AAF zone xx, activated
.... during the Investigation Period (I Period):
AAF zone xx, investigation in progress
The AAF zone xx (xx=00-99) is only valid for the c.i.e. it is shown in,
i.e. not for the whole system.
NOTE!
All devices belonging to an AAF zone must be connected to one c.i.e.
100