Panasonic EBL512 G3 Planning Instructions page 64

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Comments to the trigger conditions:
0. Default. The input does not work.
1. Key cabinet, where the fire brigade store there key to the building.
Will activate a Key cabinet alarm.
Instructions for more information.
2. Alert annunciation, see EBL512 Operating Instructions for more
information.
3. Like 2.
4. Ext. power supply equipment fault output will activate a fault in
the EBL512 system. The following fault message will be shown:
FAULT: External power supply, CU xx
5. Ext. fuses (for the ext. power supply equipment) fault output will
activate a fault in the EBL512 system.
message will be shown:
FAULT: External fuses, control unit xx
6. External clock, timer, key switch, etc. can disable / re-enable
alarm points. The function Alert Annunciation, etc. can be set on
/ off by a time channel. Control outputs can be set on / off by a
time channel.
7. A special detector, push button, etc. can activate a fire alarm in
EBL512. Zone no. and Address (+ user definable text).
8. Activated Fire brigade tx feedback to the EBL512 control unit to
light up the LED "Fire brigade tx".
9. Activated Extinguishing equipment feedback to the EBL512
control unit to light up the LED "Extinguishing".
10. Activated Ventilation equipment feedback to the EBL512 control
unit to light up the LED "Ventilation".
11. Ext. fault will activate a fault in EBL512. An user definable fault
message ("Error text") up to 40 characters, will be shown.
12. Used to start a new "countdown", see 13 below.
Push button: NO, momentary action. One or more push buttons
can be used.
13. Output for Extinguishing equipment (type of output = 2) has
normally a delayed activation (a "countdown").
"countdown" will be stopped when an input with trigger condition
13 is activated. To start a new "countdown", see 12 above.
Push button info: NO, latching action. One or more push buttons
can be used. Manual reset of push button(s).
14. A feed-back from the equipment activated by the corresponding
interlocking output. Activated input is shown in menu H9/C1.
See also chapter "Interlocking function", page 79.
50
One input activated in any control unit, will light up the LED respectively
in all control units.
See EBL512 Operating
50
50
62
The following fault
50
This

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents