Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
26
Loss of mains (in a c.i.e. or output unit 2262). NOTE!
The output(s) will be activated immediately but the
corresponding fault is normally delayed.
27
This control expression is true for 5 seconds, whenever a
reset pulse is sent to the specified zone/address. The
control expression can only be used in the same c.i.e. as
the specified zone/address.
28
The programmed time channel (1-63) is activated.
29
Alert Annunciation activated (by any alarm point set to
activate this function). Valid until the AA alarm is reset
or becomes a normal fire alarm. For more information,
see EBL512 G3 United version 2.7.x Operating
Instructions.
30
Alert Annunciation activated (by any alarm point set to
activate this function) and acknowledged. Valid until the
AA alarm is reset or becomes a normal fire alarm. For
more information, see EBL512 G3 United version 2.7.x
Operating Instructions.
31
Door open in the specific control unit.
32
Door open in any control unit in the system.
33
General Key cabinet alarm. For more information, see
EBL512 G3 United version 2.7.x Operating Instructions.
34
General control disabled (via menu H2/B7).
output should be of type Control – neutral.
35
Control disabled for a specific control unit (via menu
70
H2/B7).
neutral.
36
General alarm device disabled (via menu H2/B8
"Silence alarm devices). This output should be of type
Control – neutral.
37
Alarm device disabled for the specific control unit (via
menu H2/B8 or via "Silence alarm devices). This output
should be of type Control – neutral.
38
This trigger condition plus the OR operator shall be used
for each detector (zone-address) controlling a fire door
(normally > two detectors). Type of output is normally
"Control, neutral".
Closing", page 83.
68
Indicated by LED "General fault" and/or LED "Fault tx activated".
69
Or ext FBPs connected to the control unit(s).
Indicated by LED "Door open".
70
Indicated by LED "Disablements".
71
Indicated by LED "Fault / Disablements Alarm devices".
72
In Danish convention (DBI), must only the c.i.e. outputs R0-R1 and S0-S3
be used. (No COM loop units.) and the type has to be "control. neutral".
This output should be of type Control –
72
See also chapter "Fire Door
74
69
69
70
This
71
or via