Selective Alarm Presentation - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
20.1.5
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Selective alarm presentation

In a system (i.e. two or more control units in a TLON network) it is
possible to choose which control units' fire alarms
presented in the control unit respectively.
Default = All fire alarms will be presented in all control units. In each
"Control unit" dialog box, the control units that shall not be presented
in that control unit have to be de-selected.
Example: A system with four Control Units (C.U. 0, 1, 2 and 3). In
C.U. 0 shall only fire alarms from C.U. no. 0 be presented and in C.U.
1, 2 and 3 shall all fire alarms be presented.
How to de-select a control unit: Select a control unit in the "Control
unit" drop down list box (e.g. 1) and empty the "Selected" check box
(on the right side). Click the "Apply" button and Selected = 1 changes
to Selected = 0.
This has to be done for control units 2 and 3 also.
"Control unit" dialog box for control unit 0. Control units 1,2 and 3
are de-selected:
Control unit
Selected
0
1
1
0
2
0
3
0
"Control unit" dialog box for control unit 1, 2 and 3 respectively. No
control unit is de-selected:
Control unit
Selected
0
1
1
1
2
1
3
1
NOTE!
The control unit relay output "Fire brigade tx" will be activated for the
fire alarms that will be presented in the control unit respectively, i.e.
all alarms or alarms from selected control units only.
116
Activated by alarm points, etc. connected to a control unit.
131
116
that shall be