Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
"Time Activation Output" 1-10 can be programmed. For each Time
Activation Output the properties have to be set:
No.:
X = The number of the Time Activation Output, 1-10.
Information only, cannot be changed.
Logical name: Normally not changed but each Time Activation
Output can have a name indicating what it is meant for, e.g. "Alarm
devices".
Type: Steady (continuous), Intermittent, One pulse, Steady – delayed
activation, Intermittent - delayed activation, One pulse - delayed
activation or Steady – delayed de-activation.
Delay time: Can be set, when required, to 0-255 x 0.8 sec.
Pulse length: Can be set, when required, to 0-255 x 0.8 sec.
Pulse off: Can be set, when required, to 0-255 x 0.8 sec.
De-activation: Can be set, when required, to 0-255 x 0.8 sec.
Min. = 1 x 0.8 = 0.8 sec. Max. = 255 x 0.8 = 204 sec. = 3 min. 24 sec.
Door open
Indication door open affected by
Not valid for EBL512 G3 United version 2.7.x control units. The
"Open door" symbol shown in the display is always indicating "any
door open in the system".
Disablement of routing equipment
No disablement (default): Door open in a C.U. or an ext. FBP
will not disable the outputs for routing equipment (Fire brigade
and fault tx).
Disable by door in any control unit: Door open in any C.U.
will disable the outputs for routing equipment (Fire brigade and
fault tx) in all C.U:s.