Definitions / Explanations; Pewn Ab; Alarm Points; Smoke Detector - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
2
2.1
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.2.6
2.2.7
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Definitions / Explanations

Definitions / explanations / abbreviations / etc. frequently used or not
explained elsewhere in the document.
PESN AB
Panasonic Eco Solutions Nordic AB

Alarm points

Units, which can generate a fire alarm (in the control unit), i.e. analog
detectors (sensors), conventional detectors, manual call points, etc.

Smoke detector

Analog and conventional photoelectric (optical) smoke detectors are
available.

Sensor

Sensor = Analog detector

Analog detector

Contains an A/D-converter. The Control Unit pick up the digital
values ("sensor values") for each detector individually.
evaluations and "decisions" are then made in the c.i.e.
detectors are addressable – an address setting tool is used for detector
types 430x.
An analog detector has to be plugged in an analog sensor base (ASB).

Analog (Sensor) Base (ASB)

An analog detector is plugged in an ASB, which is connected to a
COM loop (see below).

Conventional detector

Detector with only two statuses, i.e. normal and fire alarm. The
detector has a closing contact and a series alarm resistor. Normally
plugged in a conventional detector base CDB (see below) connected
to a conventional zone line input, with an end-of-line device. Some
types (e.g. water proof types) are connected directly on zone line.

(Conventional Detector) Base (CDB)

A conventional detector is plugged in a CDB, connected to a
conventional zone line input.

Addressable

A unit with a built-in address device, i.e. each unit is individually
identified, handled and indicated in the c.i.e.
(The unit can be an I/O unit with a zone line input, to which one or
more conventional "alarm points" can be connected.)
11
All
Analog

Hide quick links: