Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
system.
(In this case also a fault will be generated, see
below.)
The input in the master will be "blocked" as follows:
 No fault on the TLON network AND Fire alarm in the system.
Presentation of fire alarm from several control units (slaves)
In the master, a fire alarm activated by any of the other control units
(slaves) will be presented as in the following example:
POINT: 999-99
User definable text message
The zone number "999" indicates that the fire alarm is activated by a
control unit. The address "99" indicates several control units (slaves)
connected in parallel. The user definable text message may be used to
indicate that the alarm originates from one or more CUs (slaves).
Presentation of fault from several control units (slaves)
An open circuit (cut-off) or short circuit on the input in the master will
generate a fault and a fault message as follows (depending on which
unit is used):
FAULT:Cut-off input n,1580 board b, CU xx
FAULT:Sh-circ input n,1580 board b, CU xx
n = zone line input (0-7) on the 1580 board.
b = 1580 board no. (0-5) in the master.
xx = control unit no. (00-29) of the master.
No fault on the TLON network AND fire alarm activated by any
control unit (slave) AND no other fire alarm in the system will,
besides the fire alarm, generate a fault and a fault message as follows
(depending on which unit is used):
FAULT: Alarm input n,1580 board b, CU xx
n = zone line input (0-7) on the 1580 board.
b = 1580 board no. (0-5) in the master.
xx = control unit no. (00-29) of the master.
117