Panasonic EBL512 G3 Planning Instructions page 43

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
9.1.1.3
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
3339 Enclosed Addressable Manual Call Point.
3333 unit but with another type of back-box (incl. a tightening
gasket). For surface mounting. For indoor use in premises
where IP56 rating is required. Operating temp. -10 to +55 °C.
Analog Detectors
3308 Analog heat detector. 3308 shall be plugged in an analog base
(3312 / 3312F / 3312FL / 4313). Built-in LED that is lit to
indicate that the detector has activated a fire alarm. Prepared
for mechanical lock (screw attached) – if required. The COM
loop address is set with the Address setting tool (3314). The
detector has an address label on which the programmed COM
loop address can be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode: 3308 is in this mode via Win512 version
2.7.x set to one of three algorithms (static response temp. range)
for class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: Not used in a mixed system.
2312 mode: This mode cannot be used for 3308.
3309 Analog heat detector. Enclosed (IP67)
lit to indicate that the detector has generated fire alarm.
Terminals for an ext. LED (2218). Recess for label holder
(3391). The COM loop address is set with the Address setting
tool (3314). The Address setting tool 3314 is also used for
mode setting:
NORMAL mode: 3309 is in this mode via Win512 version
2.7.x set to one of three algorithms (static response temp. range)
for class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: Not used in a mixed system.
2312 mode: This mode cannot be used for 3309.
4300 Analog multi detector. 4300 is a smoke detector and a heat
detector within one housing. Scattered light (i.e. reflection of
infrared light) is used to detect smoke and the heat sensing
element is a thermistor. The detector unit (actually the heat
detector) can detect a methylated spirits (alcohol) fire (EN54-9,
test fire TF6; liquid fire), which normally is impossible for a
photo electric smoke detector to detect.
The detector has unleaded soldering.
24
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 70°C), -20°C < T
24
. Built-in LED that is
< 65°C.
a
41
23
3339 is like the