Fan Control - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
6.4.2
6.4.3
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Each output (0-47) has to be added and programmed via Win512
version 2.7.x regarding:
Output no. (0-47)
Properties, like any programmable relay output.
Each input (0-15) has to be added and programmed via Win512
version 2.7.x regarding:
Input no. (0-15)
Triggered by = Type (of input)
Properties, like any programmable input.

Fan control

Used for Application board type Fan control, e.g. "Fan control
application board" 4594, which has a front for Fan control of up to
four fans.
Fan control panel 4593 has two Fan control application boards 4594
and two Fan control fronts (see page 53).
Each Fan (0-3) (i.e. each Fan control) has to be added and
programmed via Win512 version 2.7.x.
For each fan (Fan control), also one I/O unit for fan control 3361
(COM loop unit) has to be added and programmed via Win512
version 2.7.x regarding e.g:
Technical number
Name (Fan control I/O unit - normally not changed)
Fan control information
 Fan number (0-3)
 Supervised or not supervised
 Output latched or not latched
 Normally stopped / normally running
Properties, like any programmable output.
Normally stopped or Normally running
Zone control
Used for Application board type Zone control.
18
Zone control is normally used on the Australian market only.
18
33