Group 35: Motor Temp Meas
This group defines the detection and reporting for a particular potential fault – motor
overheating, as detected by a temperature sensor. Typical connections are defined
below.
One Sensor
Motor
T
10 nF
Warning! IEC 60664 requires double or reinforced insulation between live
parts and the surface of accessible parts of electrical equipment which are
either non-conductive or conductive but not connected to the protective earth.
To fulfil this requirement, connect a thermistor (and other similar components)
to the drive's control terminals using any of these alternatives:
• Separate the thermistor from live parts of the motor with double reinforced
insulation.
• Protect all circuits connected to the drive's digital and analog inputs.
Protect against contact, and insulate from other low voltage circuits with
basic insulation (rated for the same voltage level as the drive's main
circuit).
• Use an external thermistor relay. The relay insulation must be rated for the
same voltage level as the drive's main circuit.
The figure below shows alternate thermistor connections. At the motor end the cable
shield should be earthed through a 10 nF capacitor. If this is not possible, leave the
shield unconnected.
Thermistor Relay: Thermistor (0) or (1)
Thermistor
relay
T
Motor
Three Sensors
1
AI
Motor
AGND
T
1
AO
AGND
Thermistor (0)
OMIO board
DI6
+24 VDC
T
Motor
T
T
10 nF
OMIO board
DI6
+24 VDC
10 nF
117
1
AI
AGND
1
AO
AGND