Input Power Cables and Fuses

Branch circuit protection must be provided by the end-user, sized per national and
local electric codes. Recommendations for fuses for short-circuit protection on the
mains cable are below.
Type
ACS550-02
Frame
ACS550-U2
Size
-196A-4
R7
-245A-4
R7
-289A-4
R7
-368A-4
R8
-486A-4
R8
-526A-4
R8
-602A-4
R8
-645A-4
R8
Note 1: Mains cable sizing is based on a correction factor of 0.71 (maximum of 4 cables laid on a cable
ladder side by side, ambient temperature 30 °C (86 °F), EN 60204-1 and IEC 364-5-523). For other
conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive. In any case, the cable must be between the minimum limit defined in this
table and the maximum limit defined by the terminal size (see
Note 2: Fuse Type: IEC 269 gG, UL Class T.
Note 3: Fuses from other manufacturers can be used, if they meet the ratings.

Cable Terminals

Mains and motor cable maximum sizes (per phase) accepted a the cable terminals,
and the tightening torques are listed below.
Frame
Number of
Size
holes per
R7
R8

Input Power (Mains) Connection

Voltage ( U
Prospective short-
circuit current
Technical Data
Cable
Cu
2
(mm
)
3x185+195
3x240+95Cu
3x240+120
2x(3x120+50Cu)
2x(3x95+50)
2x(3x150+50Cu)
2x(3x150+95)
2x(3x240+95Cu)
2x(3x240+120) 3x(3x150+50Cu)
3x(3x150+95)
3x(3x240+95Cu)
3x(3x185+95)
3x(3x240+95Cu)
3x(3x185+95)
3x(3x240+95Cu)
U1, V1, W1, U2, V2, W2
Cable diameter
phase
mm
in
2
58
2.28
3
58
2.28
Input Power (Mains) Connection Specifications
)
400/415/440/460/480 VAC 3-phase +10% -15% for 400 VAC units
1
Maximum allowed prospective short-circuit current in the supply is 65 kA in
a second providing that the mains cable of the drive is protected with
(IEC 629)
appropriate fuses. US: 65,000 AIC.
Frequency
48...63 Hz
Imbalance
Max. ± 3% of nominal phase to phase input voltage
Al
A
V
2
(mm
)
250
500
250
500
315
500
400
500
500
500
630
500
630
500
800
500
Cable Terminals
Tightening
Screw
Torque
Nm
lb-ft
M12
50...75
35...55
M12
50...75
35...55
Fuses
Manufacturer
Type
ABB Control
OFAF1H250
ABB Control
OFAF1H250
ABB Control
OFAF1H315
ABB Control
OFAF1H400
ABB Control
OFAF1H500
ABB Control
OFAF1H630
ABB Control
OFAF1H630
ABB Control
OFAF1H800
on page
182
).
Earthing PE
Tightening
Screw
torque
Nm
M8
15...22
M8
15...22
IEC
-size
1
1
2
2
3
3
3
3
lb-ft
10...16