Complete Parameter Descriptions

This section describes the actual signals and parameters for ACS550.
Group 99: Start-up Data
This group defines special Start-up data required to:
• Set up the drive.
• Enter motor information.
Code Description
9901 LANGUAGE
Selects the display language.
0 =
ENGLISH
5 =
PORTUGUES
10 =
SVENSKA
9902 APPLIC MACRO
Selects an application macro. Application macros automatically edit parameters to configure the ACS550 for a
particular application.
1 =
ABB STANDARD
6 =
PID CONTROL
0 =
1
USER S
LOAD
9904 MOTOR CTRL MODE
Selects the motor control mode.
1 =
: s
– sensorless vector control mode.
VECTOR
PEED
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
, or 2001
MAXIMUM SPEED
speed).
2 =
:
.
VECTOR
TORQ
• Reference 1 is speed reference in rpm.
• Reference 2 is torque reference in % (100% is nominal torque.)
3 =
:
– scalar control mode.
SCALAR
SPEED
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM FREQUENCY
than the maximum speed).
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
• Must equal the value on the motor rating plate.
• The ACS550 cannot supply the motor with a voltage greater than the
mains voltage.
9906 MOTOR NOM CURR
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: (0.2...2.0) · I
9907 MOTOR NOM FREQ
Defines the nominal motor frequency.
• Range: 10...500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the
.
VOLT
• Field weakening point = Nom Freq * Supply Volt / Mot Nom Volt
Start-Up
1 =
(
)
2 =
ENGLISH
AM
6 =
7 =
NEDERLANDS
2 = 3-
3 =
WIRE
7 =
8 =
PFC CONTROL
-1 =
1
-2 =
USER S
SAVE
if the absolute value of the minimum speed is greater than the maximum
MINIMUM SPEED
, or 2007
MINIMUM FREQUENCY
(where I
is drive current).
2hd
2hd
3 =
DEUTSCH
ITALIANO
8 =
FRANCAIS
DANSK
4 =
ALTERNATE
MOTOR POT
TORQUE CTRL
2
-3 =
USER S
LOAD
USER S
if the absolute value of the minimum speed is greater
Output voltage
P 9905
MOTOR NOM
4 =
ESPAÑOL
9 =
SUOMI
5 =
/
HAND
AUTO
2
SAVE
Output
frequency
P 9907