Ambient Conditions - ABB ACS550-02 User Manual

Drives 110/150...355 kw/550 hp
Hide thumbs Also See for ACS550-02:
Table of Contents

Advertisement

Ambient Conditions

The following table lists the ACS550 environmental requirements.
Altitude
Ambient
temperature
Relative
humidity
Contamination
levels
(IEC 721-3-3)
vibration
(IEC 60068-2)
Shock
(IEC 68-2-29)
Free fall
Ambient Environment Requirements
Installation Site
• 0...1000 m (0...3,300 ft)
• 1000...2000 m (3,300...6,600 ft) if
P
and I
derated 1% every 100 m
N
2
above 1000 m (300 ft above 3,300 ft)
• -15...40 ºC (5...104 ºF)
• Max. 50 ºC (122 ºF) if P
N
derated to 90%
< 95% (non-condensing)
• No conductive dust allowed.
• The ACS550 should be installed in
clean air according to enclosure
classification.
• Cooling air must be clean, free from
corrosive materials and free from
electrically conductive dust.
• Chemical gases: Class 3C2
• Solid particles: Class 3S2
• Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz) sinusoidal
Not allowed
Not allowed
Storage and Transportation in the
protective package
-40...70 ºC (-40...158 ºF)
and I
2
Storage
• No conductive dust allowed.
• chemical gases: Class 1C2
• solid particles: Class 1S2
Transportation
• No conductive dust allowed.
• Chemical gases: Class 2C2
• Solid particles: Class 2S2
Storage
• Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
max. 7 m/s
(13.2 to 100 Hz) sinusoidal
Transportation
• Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
(9 to 200 Hz) sinusoidal
2
max. 100 m/s
• 100 mm (4 in) for weight over 100
kg (220 lb)
185
2
(23 ft/s
)
2
2
(49 ft/s
)
2
(330 ft/s
), 11ms (36 fts)
Technical Data

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-u2Acs550-01Acs550-u1