Alarm
Display
Code
2008
PANEL LOSS
2009
Reserved
2010
MOT OVERTEMP
2011
UNDERLOAD
2012
MOTOR STALL
2013
AUTORESET
(note 1)
2014
AUTOCHANGE
(note 1)
2015
PFC INTERLOCK
2016
Reserved
2017
2018
PID SLEEP
(note 1)
Note 1. Even when the relay output is configured to indicate alarm conditions (e.g. parameter
1401
1 = 5 (
RELAY OUTPUT
ALARM
Panel communication is lost and either:
• Drive is in local control mode (the control panel displays LOC), or
• Drive is in remote control mode (REM) and is parameterized to
accept start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections
• Parameter 3002
PANEL LOSS
• Parameters in groups 10
(if drive operation is REM).
SELECT
Motor is hot, based on either the drive's estimate or on temperature
feedback. This alarm warns that a Motor Underload fault trip may be
near. Check:
• Check for overloaded motor.
• Adjust the parameters used for the estimate (3005...3009).
• Check the temperature sensors and Group 35 parameters.
Motor load is lower than expected. This alarm warns that a Motor
Underload fault trip may be near. Check:
• Motor and drive ratings match (motor is NOT undersized for the
drive)
• Settings on parameters 3013 to 3015
Motor is operating in the stall region. This alarm warns that a Motor
Stall fault trip may be near.
This alarm warns that the drive is about to perform an automatic fault
reset, which may start the motor.
• To control automatic reset, use parameter group 31 AUTOMATIC
RESET.
This alarm warns that the PFC autochange function is active.
• To control PFC, use parameter group 81 PFC CONTROL and
Application Macro: PFC
This alarm warns that the PFC interlocks are active, which means that
the drive cannot start the following:
• Any motor (when Autochange is used),
• The speed regulated motor (when Autochange is not used).
This alarm warns that the PID sleep function is active, which means
that the motor could accelerate when the PID sleep function ends.
• To control PID sleep, use parameters 4022...4026 or 4122...4126.
) or 16 (
/
)), this alarm is not indicated by a relay output.
FLT
ALARM
Description
.
and 11
COMMAND INPUTS
REFERENCE
on page
59
.
171
Diagnostics