Protecting the Relay Output Contacts and Attenuating Disturbances in
Case of Inductive Loads
Inductive loads (relays, contactors, motors) cause voltage transients when switched
off.
It is highly recommended to equip inductive loads with noise attenuating circuits
[varistors, RC filters (AC) or diodes (DC)] in order to minimize the EMC emission at
switch-off. If not suppressed, the disturbances may connect capacitively or
inductively to other conductors in the control cable and form a risk of malfunction in
other parts of the system.
Install the protective component as close to the inductive load as possible. Do not
install protective components at the OMIO board terminal block.
Varistor
230 VAC
RC filter
230 VAC
Diode
24 VDC
OMIO
X1
Digital outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
13