Mitsubishi Electric MELSEC iQ-R Series User Manual page 110

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
Open System
Sending Interval Monitoring Time [ms]
Safety Refresh Monitoring Time [ms]
Safety Data Transfer
Receive Data
Device Setting
Storage Device
Send Data Storage
Device
Safety Authentication Code
[Output to File (for Setting Confirmation)]
button
*1 When the settings cannot be determined with the module parameter and "Network Configuration Settings", a hyphen or incorrect
calculation result may be displayed.
*2 Set the safety connection number starting with 1.
Even if the safety connection is set in a random line, the unset line is deleted and the number is set starting with 1 when the [OK] button
is clicked.
*3 Safety communications are sent/received in increments of 32 points, however a safety data transfer device setting can be set in
increments of 16 points.
2 PARAMETER SETTINGS
108
2.3 Basic Settings
Description
Open system of the own station is displayed.
In each safety connection, set sending interval monitoring time
for a receiving station to detect safety communication errors.
In each safety connection, set safety refresh monitoring time for
a receiving station to detect safety communication errors.
Set a safety device of the Safety CPU where safety data are
received.
Set a safety device of the Safety CPU where safety data are
sent.
This code is used to identify the communication destination
when safety communications perform. Set the same value in the
master station and slave station to perform the safety
communications.
When the communication destination is set to a local station, the
safety approval code is masked with blank.
Outputs the contents of the safety communication setting to a
CSV file. The file is used to check whether there is no
discrepancy between the safety communication setting written to
the Safety CPU and that of the project.
( GX Works3 Operating Manual)
Setting range
• When the own station is the master
station: Active (Fixed)
• When the own station is a local station:
Passive (Fixed)
(Default: empty)
3.0 to 1000.0 (Default: empty)
4.0 to 2000.0 (Default: empty)
■Device name
• SA\X
• SA\M
• SA\B
• SA\D
• SA\W
(Default: empty)
■Points
• Bit device: 16 to 128 (set in increments of
*3
16 points)
• Word device: 1 to 8 (set in increments of
1 point)
(Default: empty)
■Start/End
Range of a safety device in the Safety CPU
(Default: empty)
■Device name
• SA\Y
• SA\M
• SA\B
• SA\D
• SA\W
(Default: empty)
■Points
• Bit device: 16 to 128 (set in increments of
*3
16 points)
• Word device: 1 to 8 (set in increments of
1 point)
(Default: empty)
■Start/End
Range of a safety device in the Safety CPU
(Default: empty)
0 to FFFFFFFFH
(Default: empty)